Description

The valve protects the pumping system from water hammer, caused by sudden pump shut-off (case of power failure, for example). The valve is assembled on a T-junction of the
main pipeline, instantly opens when the pump stops, relieving the returning high pressure wave. The valve slowly closes once the pressure returns to the static level. The valve also functions as a pressure relief valve.
 
Features
  No slam operation
Simple and reliable design
Easy installation and maintenance
Low Resistance and high flow capacity
Protection for sewage as well as clean water pumping systems

Purchase Specifications
The valve will be hydraulic, direct sealing diaphragm type, which allows inline maintenance. No stem, shaft or guide bearing will be located within the water passage. The valve will be activated by the line pressure or by an external hydraulic or pneumatic pressure. The valve will be operated
by pressure relief pilot valve for opening at a low pressure set point and another pilot for pressure relief at a high pressure set-point. The valve and the controls will be a Dorot Series 100 valve or similar in all aspects.
 
Quick Sizing
  The valve should be sized to match the 80% of the normal flow at static head in the valve site:
D[mm] ≤ √(250 x Flow[m3/hr] /
√Pressure[mwc])
D[inch] ≤ √(0.109 x Flow[gpm] /
√Pressure[psi])

Design Considerations
  Install a manual separation/throttling valve, upstream of the valve position
  Closure time is related to the pipe length and should be extended for longer pipe
The valve sensor tube must be connected to the main line

 






 


Optional Control System Components:

1.  Main Valve
2. Self-flushing filter
3. Cock valve*
4. Low-pressure relief pilot valve
5. High-pressure relief pilot valve
6. Needle valve
7. Pressure gauge

* Optional component




 


Typical Application

Dorot Surge Anticipating Valve prevents water-hammer/surges caused by an un-expected pump shut-off.


© Copyright Dorot 2014 | Sitemap | Privacy Policy
Control Valves | Products | Articles | News | About Us | Standards | Contact Us | Sprinkler Systems Valves | Distributors | Catalogues | Air valves | Water meters | Mining Valves | Irrigation Valves | Agricultural Valves | Waterworks Valves | Plastic Valves | Fire protection mechanical valves | Fire Protection | Construction & Industry | Filtration & Water treatment | Wafer Valves | Filters Back-Flushing Control Valves | Gate Valves | Flanged Valves | Swing Check Valve | Double-Flap Check Valve | Power station valves |