Waterworks
Irrigation
Fire Protection
Construction & Industry
Filtration & Water treatment
Others
SEE ALSO
 Technical Data
Products  >  100 Series (GAL)  >  Control Functions  >  100BC Booster Pump Control Valve  >    

100BC Booster Pump Control Valve


Description

The valve eliminates damaging surges caused by pump start-up and shut-off. The electrically activated valve
gradually opens on pump start up, and slowly closes before the pump is switched off. The valve will automatically close drip tight in case of power failure. Optional Additions: Flow Rate Limitation, Extended Closure, Two Stage Operating,
Pressure Reducing and Pressure Sustaining.
 
Features
  No slam operation
Exceptionally low losses at high flow conditions
Simple and reliable design
Easy installation and maintenance

Purchase Specifications
The valve will be hydraulic, direct sealing diaphragm type, which allows inline maintenance. No stem, shaft or guide bearing will be located within the water passage. The valve will be activated by the line pressure or by an external hydraulic or pneumatic pressure. The valve position will be controlled by an electric solenoid valve with adjustable open/close speed control valves. The valve and the controls will be a Dorot Series 100 valve or similar in all aspects.
 
Quick Sizing
  Valve size same as line or one size smaller
  Maximum flow speed for continuous operation 5.5 m/sec (18 ft/sec)

Design Considerations
  The valve should be suited for the maximal flow
  Closure time is related to the pipe length and should be extended for longer pipe
For power failure situations, add a fast reacting checkvalve in series and a surge anticipating valve to relief possible surges

 





 


Optional Control System Components:

1.  Main Valve
2. Self-flushing filter
3. Cock valve*
4. 3/2 Solenoid valve
5. Accelerator relay (optional for valves larger than 150mm/6")
6. Open/close speed adjustment needle valve
7. Check valve
8. Limit switch assembly

* Optional component




 


Typical Application

Dorot Booster Pump Control Valve preventing surges caused by pump startup and shutoff and drainage of main pipe.


© Copyright Dorot 2017 | Sitemap | Privacy Policy
Control Valves | Products | Articles | News | About Us | Standards | Contact Us | Sprinkler Systems Valves | Distributors | Catalogues | Air valves | Water meters | Mining Valves | Irrigation Valves | Agricultural Valves | Waterworks Valves | Plastic Valves | Fire protection mechanical valves | Fire Protection | Construction & Industry | Filtration & Water treatment | Wafer Valves | Filters Back-Flushing Control Valves | Gate Valves | Flanged Valves | Swing Check Valve | Double-Flap Check Valve | Power station valves |